Section 38 – Sewer and Storm Drain Construction
12/1/03
38.17
38-10.02.D Hydrostatic Test for Leakage – Storm Drain
If, in the opinion of the Inspector, excessive groundwater is encountered in the construction
of a section of the storm drain, the exfiltration test for leakage shall not be used.
The end of the storm drain at the upper structure shall be closed sufficiently to prevent the
entrance of water, and pumping of groundwater shall be discontinued for at least three (3)
Calendar Days, after which the section shall be tested for infiltration.
The infiltration into each individual reach of storm drain between adjoining manholes shall
not exceed five hundred (500) gallons per inch of internal diameter per mile per day.
The allowable infiltration for any portion of the storm drain system shall be measured by a
weir or current meter placed in the appropriate manhole.
38-10.02.D.(1) Water Exfiltration Test
The allowable water exfiltration for any length of the storm drain pipe between manholes
shall be measured and shall not exceed five hundred (500) gallons per inch of internal pipe
diameter per mile of pipe per day. The maximum testing pressure at any joint shall be five
pounds per square inch (5 psi) or eleven and one-half feet (11.5’) of head. If it is not possible to
test the pipe to five pounds per square inch (5 psi), the system shall be tested to the surface of
the lowest manhole or inlet rim in the section tested. In lieu of water exfiltration testing, the
Contractor may perform air testing as described below.
The Contractor is responsible for providing all equipment, materials, water and labor for
performing infiltration and exfiltration tests and making measurements. Payment for these items
will be included in the bid items for pipes and manholes. All tests shall be made in the presence
of the Inspector.
38-10.03 Tests for Deflection
38-10.03.A Sewer
Unless otherwise shown or specified in these Specifications or in the Contract, where PVC,
ABS, or HDPE pipe are installed as sewer a deflection test shall be made by the Contractor
upon completion and acceptance by the Agency of all backfill operations and prior to the
placement of the aggregate base, if any. Deflection testing shall be conducted no sooner than
thirty (30) Calendar Days following completion and acceptance of all backfill operations, unless
otherwise approved by the Agency.
The deflection testing will be witnessed by the Agency and shall be conducted by the
Contractor at the Contractor’s expense. One-hundred percent (100%) of all mainline PVC,
ABS, or HDPE sewer installed shall be deflection tested for excessive vertical deflection using a
pre-sized, rigid mandrel or "Go-No-Go" device approved by the Agency. The mandrel size shall
be clearly labeled and shall be sized so as to provide a diameter of at least ninety-seven
percent (97%) of the base internal diameter as specified in ASTM Designations: D 3034 or D
2680 for PVC, and ABS or AASHTO Designations: M294 or MP7-97 Type S or Type D for
HDPE. The mandrel shall be drawn through the pipe using only the force that can be exerted
by one man on the end of a rope, using no mechanical advantage. Under no conditions shall
the mandrel device be attached to the cleaning ball.
The Contractor shall remove, replace, and retest any pipe section through which the
mandrel is unable to pass. The use of any rerounding device or similar method to correct or
reduce over deflection will not be permitted. Re-tests for deflections shall be made at the
Contractor’s expense.



This Section: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Sections
: 1 2 3 4 5 6 7 8 9

Remodeling a home can be costly and frustrating, especially in decor of kitchen cabinets, veneer, bathrooms, vinyl siding, arts / crafts, patio enclosures, replacement windows doors, furniture, swimming pools spa, home security, or other architecture areas. Free Add Site 1, 2, 3, 4, 5, 6, 7
 

ADT Home Security - Replacement Windows - Home Improvement Ideas - Vinyl Siding Prices - Shopping - Bat Pest Control
Swimming Pools / Spa - Kitchen Cabinet Remodeling - Patio Enclosures - Site Map - Add URL Real Estate

Copyright © 2004 - 2008 Swimming Pools by Site-Found

Art / Decor Business / Companies Computers / Accessories Education / Schools Entertainment / Books Health / Environment Home and Garden Home Improvement / Decorating Home Sales / Real Estate Life / Homes Literature / Classics Miscellaneous Recreation / Sports Science / Technology Shopping / Gifts Society / Family Websites / Logos Favorites Add URL 2 3 4 5 6