Section 38 – Sewer and Storm Drain Construction
12/1/03
38.9
38-10.02.B Hydrostatic Test for Leakage - Sewer
A section of line shall be prepared for testing by plugging the upper side of the downstream
manhole and all openings in the upstream manhole except the downstream opening. Care shall
be exercised in installing plugs to avoid interrupting service to existing sewer or storm drain
services. Where grades are slight, two (2) or more sections between manholes may be tested
at once. Where grades are steep and excessive heads would result by testing from one
manhole to another, test tees, the same size as the main, shall be installed at intermediate
points so the maximum head on any section under test shall not exceed twelve feet (12’).
A section of line prepared as above shall be tested by filling with water to an elevation five
feet (5’) above the top of pipe at the upstream end of the test section, or five feet (5’) above the
existing ground water elevation, whichever is greater. The water shall be introduced into the
test section at least four (4) hours in advance of the test period to allow the pipe and joint
material to become saturated with water. The water level should then again be brought to the
five-foot (5’) mark. At the beginning of the test, the elevation of the water in the upper manhole
shall be carefully measured from a point on the manhole rim or test tee. After a period of four
(4) hours, or less with the approval of the Agency, the water elevation shall be measured from
the same point on the manhole rim and the loss of water during the test period calculated. If
this calculation is difficult, enough water shall be measured into the upper manhole to restore
the water to the level existing at the beginning of the test, and the amount added taken as the
total leakage.
Unless otherwise specified in the Special Provisions, the allowable leakage in the test
section shall not exceed fifty (50) gallons per mile per day per inch diameter of pipe tested at
the five-foot (5’) test head. If it is necessary or desirable to increase the test head above five
feet (5’), the allowable leakage will be increased at the daily rate of fifty (50) gallons for each
foot of increase in head.
Test sections showing leakage in excess of that allowed shall be repaired or reconstructed
as necessary to reduce the leakage to that specified above.
Water used in testing shall be disposed as directed by Agency. No testing water shall be
allowed to enter the existing sanitary sewer system.
38-10.02.C Air Test for Leakage - Storm Drain
Only lines tested after backfilling to final grade will be considered for acceptability.
However, this test may also be used by the installer as a presumptive test to determine the
condition of the line prior to backfilling.
The Contractor shall furnish all the necessary equipment and be responsible for conducting
all low-pressure air tests. In addition, the Contractor is responsible for any necessary repair
work on sections that do not pass the test. No sealant shall be used in any newly installed
storm drain without the prior approval of the Agency. Using sealant in a storm drain is not the
equivalent of a sound storm drain pipe. Proper structural repair work may be required by the
Agency.
The Agency will witness all low-pressure air tests and verify the accuracy and acceptability
of the equipment utilized.
38-10.02.C.(1) Plug Restraint
Restraints must be provided for plug to prevent blowouts of the plug. As an example of the
hazard, a force of two hundred fifty (250) pounds is exerted on an eight-inch (8”) plug by an
internal pipe pressure of five pounds per square inch, gauge (5 psig), and a force of two
thousand two hundred fifty (2,250) pounds is exerted on a twenty-four-inch (24”) plug by an
internal pressure of five pounds per square inch, gauge (5 psig). Sudden expulsion of a poorly
installed plug or of a plug that is partially deflated before the pipe pressure is released can be
very dangerous. For this reason, it is recommended that every plug be positively braced
against the manhole walls, and that no one be allowed in the manhole adjoining a line being



This Section: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Sections
: 1 2 3 4 5 6 7 8 9

Remodeling a home can be costly and frustrating, especially in decor of kitchen cabinets, veneer, bathrooms, vinyl siding, arts / crafts, patio enclosures, replacement windows doors, furniture, swimming pools spa, home security, or other architecture areas. Free Add Site 1, 2, 3, 4, 5, 6, 7
 

ADT Home Security - Replacement Windows - Home Improvement Ideas - Vinyl Siding Prices - Shopping - Bat Pest Control
Swimming Pools / Spa - Kitchen Cabinet Remodeling - Patio Enclosures - Site Map - Add URL Real Estate

Copyright © 2004 - 2008 Swimming Pools by Site-Found

Art / Decor Business / Companies Computers / Accessories Education / Schools Entertainment / Books Health / Environment Home and Garden Home Improvement / Decorating Home Sales / Real Estate Life / Homes Literature / Classics Miscellaneous Recreation / Sports Science / Technology Shopping / Gifts Society / Family Websites / Logos Favorites Add URL 2 3 4 5 6