General Construction Specifications
PART 1 - GENERAL
01 SECTION INCLUDES
A. Lighting contactors.
B. Enclosures.
02 REFERENCES
A. ANSI/NEMA ICS 6 - Enclosures for Industrial Controls and Systems.
B. NEMA ICS 2 - Industrial Control Devices, Controllers, and Assemblies.
03 SUBMITTALS
A. Submit product data under provisions of applicable Sections of Division 1.
PART 2 - PRODUCTS
04 ACCEPTABLE MANUFACTURERS - CONTACTORS
A. General Electric.
B. Square D.
C. Westinghouse.
2.02 LIGHTING CONTACTORS
A. Contactors: NEMA ICS 2; electrically held wire control.
B. Coil Operating Voltage: 120 volts, 60 Hertz.
C. Contacts: 20 amperes, 3 poles, 600 volts, 60 Hertz.
D. Enclosure: ANSI/NEMA ICS 6; Type 1.
E. Provide solderless pressure wire terminals.
F. Provide 120 Volt control transformer if needed.
PART 3 - EXECUTION
05 INSTALLATION
A. Install in accordance with manufacturer's instructions.
END OF SECTION